Product Description:
The LDU-20 modules (variants: 46WLDU20OE vers. 4.0, 46WLDU20ATX vers. 2.0 and 46WLDU20OE_SP)
are microprocessor based display and Ethernet gateway units, acting as an operator interface.
The LDU-20 modules consist of the following main features:
Power supply: Two redundant power supply 18-32Vcc isolated from ground; Both power supply voltages are monitored
Display: Size: 6,5" ; Resolution: 640 x 480 pixel ; Video: Full VGA ; Colours: 16 bit ; LED backlight intensity adjustable
Controls: Membrane push buttons are available in the lower part of the display;
LED indications:
- Four software controlled LEDs for indication provided in front panel
- Button backlight fully adjustable by software (only for 46WLDU20OE)
LED diagnostics: Five diagnostics LEDs are provided on the backside of the module
Buzzer: Fixed frequency 2 - 4kHz (option)
I/O Channels:
2x CAN-BUS: - WE-CAN+, CAN open 2.0 B compliant (1 Mbit/s), not isolated
1x CAN-BUS: - WE-CAN+, CAN open 2.0 Bcompliant (500kbit/s), isolated
2x ETHERNET: - 10 /100 Mbps (redundant) individual isolation per channel
1x USB 1.1; 1x RS-485 (230kbit/s, configurable, isolated); 2x RS-232 (115 kbit/s, not isolated)
4x Digital input: - to ground; 1x Analogue output: - 4-20mA (600Ohm), wirebreak detection
Documentation:
Parker Hannifin: - 2314AZ_Main_assembly_14; 2314_Module_Description_LDU20_Rev4_0;
- 2314_Panel_comp_assembly_LDUADA02; 2532AZ_LDU-20 ATX Main Assembly_03; 46WLDU20ATX ver 2.1 Partslist;
- 46WLDU20CA rev 2 Schema; 46WLDU20EB rev 4 Schema; 46WLDU20EB_ver4_component_assembly;
- 46WLDU20OE ver 4.1 Partslist; 46WLDU20PRO_P06_component_assembly; 46WLDU20PRO_P06.1_schematic;
Wartsila: - LDU-20 requirement specification rev_f;
Test Reports:
Vansco/Parker: - Test Plan LDU-20 Project number 314 and LDU-20 additional EMC test plan 7
Nemko Oy: - 129018B dated 17.06.2009; 129018D dated 17.03.2010; 147393 dated 30.03.2010
SGS Finko Ltd.: - 14048 dated 26.04.2010; HELEM2106000272-1 dated 24.08.2021 and
HELEM2110000409 dated 07.10.2021
VTT Expert Services Ltd.: - VTT-S-02085-10 dated 10.03.2010; VTT-S-04163-14 dated 15.09.2014 and
VTT-S-05655-17 dated 19.10.2017
The LDU-20 modules have been tested and fulfils the conditions mentioned in IACS UR E10, rev. 7.
Remarks:
The present certificate does not include the approvals of :
a) Application Software ; b) Specific functionalities related to the engine.
Following documents are to be sent for approval before of each installation on board:
- F.M.E.A document of the complete engine control system. (according to the actual configuration)
- System Block diagram complete of the connections among the modules
- Application software revision
This certificate replaces the previous certificate No. ELE220716XG/002.