Components
- DC Circuit breakers / DC-bus tie device
Model Types:
Ident number | Description | Nominal current | Size | No. Modules |
AA-10411-101 | DC-Breaker 0.5 kA - 1.5 kV | 500 A | smal | 1 |
AA-10411-111 | DC-Breaker 0.35 kA - 1.5 kV | 350 A | small | 1 |
AA-10411-102 | DC-Breaker 1.25 kA - 1.5 kV | 1250 A | medium | 1 |
AA-10411-112 | DC-Breaker 1.1 kA - 1.5 kV | 1100 A | medium | 1 |
AA-10411-122 | DC-Breaker 1.5 kA - 1.5 kV | 1500 A | medium | 1 |
AA-10411-103 | DC-Breaker 3.0 kA - 1.5 kV | 3000 A | large | 2 |
AA-10411-113 | DC-Breaker 2.25 kA - 1.5 kV | 2250 A | large | 2 |
.
General Specification |
Parameter | Min | Max | Unit | Notes |
| DC Link voltage | 0.01 | 1500 | V |
|
| DC Link nominal current | 0.35 | 3.0 | kA |
|
| System loop inductance |
| 100 | µH | 1 |
| Breaking time |
| 10 | µs | 3 |
| Breaking current |
| 20 | kA | 3 |
| Clearance time |
| 625 | µs | 2, 3 |
| 24 V Power | 16 | 100 | W |
|
| Link Length |
| 30 | m | 6 |
| Ambient temperature | 5 | 60 | °C |
|
| Water inlet temperature |
| 49 | °C | 4 |
| Humidity |
| 95 % | RH | 5 |
| IP grade electronic |
| IP54 |
|
|
| IP grade switch |
| IP54 |
|
|
Notes:
1. System inductance is not limiting factor but does have influence on overvoltage protection
2. Depends on customer system (inductance, voltage, current)
3. Refer to Astrol "Manual Marine DC-Breaker" doc.No. AD-10811-020 rev. 2.7
4. Tap water or deionized water is applicable
5. Non-condensing
6. Any optical link
Software Package | FPGA FW | CPU Appliation | MU4HV FW | GDU FW | CU4FAN Fw |
| DC-Breaker | 1.46 | 2.1 | 1.07 | 1.0 | 1.04 |
TYPE APPROVAL CERTIFICATE |
No. ELE154425XG |
Enclosure - Page 2 of 2 |
AA-10411 Series |
Other Conditions
The DC Breaker is a (bi-) directional fault current suppressor based on current interruption by switching of insulated gate bipolar transistors (IGBT).
The device is used for fault current suppression and does not replace circuit breakers or switches for isolation.
The system design need to be approved on a case-by-case basis, and must include, as part of the overall system arrangement:
- means for manual, local, operation independent of higher-level automation system, enabling necessary means for local operation, local/remote change over, and interface for setting of parameters
- means for monitoring and indication of operating status and alarms
- back-up protection (e.g. fuses) in accordance with relevant rule requirements (if applicable)
- documentation