Product description:
MD9902-Ex: 3IR Flame detector
Automatic addressable flame detector able to provide fire alarm in case of flame presence.
The MD9902-Ex is the Ex version (Flameproof Exd) of the MD9902 flame detector.
It can be used either connected to the Loop of a Fire Detection System of Microdata Due and as standalone detector.
The flame is detected by three sensors working simultaneously; one of them is working on the hot carbon dioxide specific flame wavelength, the two other measure the interference radiation on the near wavelengths.
Sensitivity Class 1, 2 , 3 as defined on the EN 54-10 Requirements is complied with.
In case a failure occurs in the fire detection and alarm system (eg. loss of communication with detectors through loop card), the degraded mode is activated and a digital signal is sent to the central unit to activate the relevant loop led on the central unit.
A signalling LED on the detector housing is also flashing when a fire alarm is detected.
The detector warns its failure conditions or degradation.
Detector housing: IP 66/ 67 _Aluminium
Reference documents:
| Microdata Due | Technical specification: | ST40100 Rev. C
RINA id. n. ELET/32832 |
| Microdata Due | Data sheets: | D40101 Rev. E
RINA id. n. ELET/32833 |
| Microdata Due | Software description: | SDD42325 Rev.0
RINA id. n. ELET/32838 |
| Microdata Due | User manual - Operating instructions: | IS41219 Rev.B - IS42308 Rev. A
RINA id. n. ELET/32835-ELET/32837 |
| Microdata Due | Risk Assessment: | D43453 Rev.0
RINA id. n. ELET/32834 |
| IMQ | ATEX - IECEx safety certificates: | IMQ 21 ATEX 062 X - IECEx IMQ 21.0015X
RINA id. n. ELET/34344-ELET/34345 |
Test reports:
| CNBOP-PIB | Performance | Test Report_1285_BA_21 (05/05/2023)
RINA id. n. ELET/32859 |
| TESLAB | Environmental | Test Report 232049F (30/03/2023) RINA id. n. ELET/32861 |