| Extinguishing agent trade name | FK-5-1-12 - CF3CF2C(O)CF(CF3)2 |
| Minimum design concentration | 5.85 % |
| NOAEL (% volume) | 10.0 |
| LOAEL (% volume) | >10.0 |
| Cylinder capacity | 27, 40, 80, 140 liters capacity |
| Storage pressure | 42 bars at 20° C (600 Psi at 68° F) |
| Operating temperature | -20° to 55° C (-4° to 131° F) |
| Assembly cylinder position | Vertical only (outside protected space) |
- Discharge nozzle: brass nozzle connection size (1/2", 3/4", 1", 1" 1/2), type TS-FK, with maximum working
pressure 42 bar;
- Container valves: brass body connection size (2" 1/2 F), type TS-27R222,with working pressure: 25 ÷42 bar;
- Container valves: brass body connection size (1" M), type TS-VRF1-N, with working pressure: 25 ÷ 42 bar.
Field of application Fixed gas fire-extinguishing systems for use in machinery spaces of category A and cargo pump-rooms
equivalent to fire-extinguishing systems required by SOLAS Ch II-2, Reg 10.5 and II-2, Reg 10.9.
Reference documents Clean Marine FK Design, installation and maintenance manual REV 01 issued by Tema Sistemi S.P.A and filed by RINA with n° CSST-18104; Discharge nozzle type TS-FK connection size 1/2", 3/4", 1", 1"1/2 issued by Tema Sistemi S.P.A and approved by RINA with n° CSST-16913; Container Valve type TS-27R222 connection size 2" 1/2 issued by Tema Sistemi S.P.A and approved by RINA with n° CSST-16914, Container Valve type TS-VRF1-N connection size 1" issued by Tema Sistemi S.P.A and approved by RINA with n° CSST-18103.Test report Fire Test report N° TS-CM-FK/01/18 issued by Brand Technology S.r.l witnessed and filed by RINA with
n° CSST-16916.Remark
This certificate annuls and replaces certificate n° MED337719CS/002 issued on March 12, 2020. |
|