MED141323CS!001ENGD- -  -  N- PROFLON FP -N- S- S- -11/07/2023- Marine Equipment- - SN- S- - N-  - 537,075B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED141323CS/001- N-Jul 10, 2028537075
 
Form
  Marine Equipment(TO)
MED063424MI/010
Certification N. MED141323CS/001 - (ENG)
Certificate date 11/07/2023
Type Protezione antincendio
Product Fixed low expansion foam fire extinguishing systems components for machinery spaces and tanker deck protection
Item Nº MED/3.58

Model or Denomin.
Items
PROFLON FP
Applicant PROFOAM SRL
Place of requester VIA MARCONI, 21  %  28060 San Pietro Mosezzo (NO)  % ITALY
Tel. N.,Fax, Email 0321 485511, 0321 485522, ---
Directive (EU) 2022/1157
Standards IMO MSC.1/Circ.1312, IMO MSC.1/Circ.1312/Corr.1.
Reference Documents SOLAS 74 Reg.II-2/10. IMO Res.MSC.98(73)-(FSS Code) 6, IMO Res.MSC.98(73)-(FSS Code) 14, IMO MSC/Circ.1239, IMO MSC.1/Circ.1276.
Request 05/04/2023
Expire date 10/07/2028
EC TYPE EXAMINATION (MODULE B) ENG
Vuoto Querysave
Paolo Brocca S

EC TYPE EXAMINATION (MODULE B)
No. MED141323CS/001

This is to certify, that RINA, specified as Notified Body Nº 0474 by the Italian "Ministero delle Infrastrutture e dei Trasporti Direzione Generale per la navigazione ed il Trasporto Marittimo ed Interno" on 25 November 1998, did undertake the relevant type approval procedures for the equipment identified below which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 96/98/EC as modified by Directive (EU) 2022/1157
MED Item Nº MED/3.58
Description Fixed low expansion foam fire extinguishing systems components for machinery spaces and tanker deck protection
Type PROFLON FP
Applicant PROFOAM SRL
VIA MARCONI, 21,28060 San Pietro Mosezzo (NO),ITALY
Testing standards applied IMO MSC.1/Circ.1312, IMO MSC.1/Circ.1312/Corr.1.
Regulations specified and reference documents SOLAS 74 Reg.II-2/10. IMO Res.MSC.98(73)-(FSS Code) 6, IMO Res.MSC.98(73)-(FSS Code) 14, IMO MSC/Circ.1239, IMO MSC.1/Circ.1276.
Issued in Genoa on
This Certificate is valid until
July 11, 2023
July 10, 2028
This Certificate consists of this sheet plus an attachment

________________________________________
Giovanni Carratino
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
No.  MED141323CS/001
Page 1 of 2

Technical Characteristics

Foam Concentrate PROFLON FP
Type of foam concentrate
Fluoroprotein low expansion foam concentrate (FP) - Type B
Mixing Ratio
3% - 6%

Density at 20°C
1,155 g/cm3

Viscosity at 20°C
8,58 cST

pH at 20°C
6,65

Lowest temperature for use
- 15 °C

Expansion Ratio at 20 °C
Mixing Ratio 3% : 7,32
Mixing Ratio 6% : 7,35
Drainage 25%
Mixing Ratio 3% : 6' 20"
Mixing Ratio 6% : 7' 32"
Field of Application

Fixed foam fire extinguishing systems using low expansion foam concentrate for extinguishing fires of following products at ambient temperature and pressure:
  • Chemical products as per list of Chapter 17, International Bulk Chemical Code (column L - letters A,B and D)
  • Chemicals products to which the IBC Code nor the BCH Code apply as per list set out in IMO MSC/Circ.553
Test Carried Out
  • Test report n° FPE 5102 - 2003/CS/01/5102 witnessed by RINA on 28/11/2003 -12/12/2003 issued in compliance to IMO MSC/Circ.582 - "Guidelines for the performance and testing criteria, and surveys of low-expansion foam concentrates for fixed fire-extinguishing systems".
Technical documentation

Datasheet PROFLON FP issued by PROFOAM and filed by RINA with n°CSST 10122.




ATTACHMENT TO
No. MED141323CS/001
Pages 2 of 2
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex B of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Giovanni Carratino
**** NOTICE: This is NOT an official certificate ****