Product description High pressure water mist system composed of water pumps, stainless steel pipes, strainer, section valves, nozzles, control and monitoring systems, or self contained system designed in accordance with the "Principal requirements of the System", IMO Res.A.800(19) as amended or IMO MSC/Circ.1165 or IMO MSC.1/Circ.1387 as amended.
Main components
| Nozzle type | EI-FOG 2Ixx0.815 |
| Extinguishing media | Fresh water /sea water |
| System activation | Manual/ Automatic |
| Pipe and fitting | Stainless steel high pressure type |
| Pump unit supply ( typical) | Voltage: 3x400V - Frequency: 50-60 Hz
Working pressure: 120 bar |
| Cylinder unit supply ( typical) | Nozzle quantity | Water quantity | Nitrogen quantity |
2 | 20.5 lt | 27 lt |
3 | 30.8 lt | 40 lt |
4 | 41.1 lt | 80 lt |
5 | 51.3 lt | 80 lt |
Field of application
Local protection for galley extract duct on conventional ships.
ATTACHMENT TO
CERTIFICATE Nr. MED144823CS
Page 2 of 3
Nozzle installation requirements
| Projection | Downwards |
| Maximum distance from each nozzle | 6500 mm |
| K factor | 0.88 |
| Minimum working pressure | 100 bar |
| Maximum duct free sectional area | 0.57 m2 |
Reference Documents
- Technical system drawings, 6482MA15/MA16/MD17/MD18 filed by RINA with n° CSST-2827.
- Technical specification "Eusebi Impianti Water Mist System for protection of galley ducts" filed by RINA with n° CSST-2829.
- Fire Extinguishing System for protection of Galley extract duct ,"Use and Maintenance Manual" issued by Eusebi Impianti and filed by RINA with n° CSST-2830
- Fire Extinguishing System for protection of Galley extract duct , "Mechanical datasheet" issued by Eusebi Impianti and filed by RINA with n° CSST-2831.
Test carried out Test Report "Eusebi Impianti EI-MIST system with EI Fog nozzle for kitchen ducts", n° 172/C, issued by Laboratorio TESI S.r.l. and filed by RINA with n° CSST-15931. |