The system is a water mist system for use in protection of Machinery Spaces of Category A or similar fire risk areas, composed of nozzles (spray heads), steel piping, manual or automatic section valves, test valves, control panel and water supply pump(s).
The system is to be designed according to principal requirements for the system, SOLAS '74 Reg.II-2/10.5.6 and IMO MSC.1/Circ.1387.
Only the nozzles are with the scope of this MED certificate.
Pumps, pipes, valves, couplings and other systems components are subject to case-by-case approval.
The open type nozzle (Type: FTCL-01) made of Stainless steel 316L with the following characteristics:
Nozzle Details |
Type | FTCL-01 |
K-factor | 4.76 |
Working Pressure | 7.5~16 bar |
Flow (using Q = K • (p)1/2) | 13.04 L/min at min.p = 7.5 bar |
The open type nozzle (Type: FTCL-01) is to be installed above the protected objects according to the following specifications:
Min. Height above the Project Objects | 0.5 m * |
Max. Height above the Project Objects | 13.5 m * |
Maximum Horizontal Spacing | 3.0 m |
Minimum pressure | p = 7.5 bar (at spray heads) |
Nozzle Arrangement Form ** | 1x1, 2x2, 1x3, 2x3 |
* Nozzles are to be installed out to a position being at the periphery of the protected objects (see IMO MSC/Circ.1387, annex 3.4.2.2), the nozzles are to be installed in a pendant (downward) position.
** Nozzles in single rows are accepted when half spacing is used, the outer nozzle should be placed at least at the edge of the protected area. |
 | ATTACHMENT TO
CERTIFICATE No. MED315623WS
Page 2 of 3 |
Continued:
Field of Application/Limitation
The nozzles are approved for use in a fixed water-based local application fire-extinguishing system for protection of Machinery Spaces of Category A or similar fire risk areas.
Reference Documents
Typical Technical Documentation, edited by Shanghai Firetec Mechatronic Engineering Co., Ltd, and approved by RINA with No.: SHFP-25083 and SHFP-25101.
Tests Carried Out
The nozzles were tested according to IMO MSC/Circ.1165 and IMO MSC.1/Circ.1387 as per below:
- Evaluation and Test Report (Ref. No.: NX2023071401) for Nozzles carried out by Nanjing Fire Laboratory Technology Co., Ltd, dated on Aug.15.2023, and filed by RINA with No.: SHFP-25095 (Stress Sorrosion Test & Vibration Test according to para. 4.11.2 & 4.15 of MSC.1-Circ.1165 were carried out under RINA Narrative Report on Lab Asessment);
- Extinguishing Fire Tests Report according to IMO MSC/Circ.1387, and filed by RINA with No.: SHFP-25093.
Installation Testing
The installation tests of the system as following:
- At least one section should be tested with full flow through the nozzles.
- Test of manual and remote release of all section valves and start of pumps.
- Testing of alarms (SOLAS Ch. II-2, Reg.10.5.6.4).
- Testing of automatic start of system (in case of unattended machinery spaces).
- Pressure testing of water pipe system.
- System to be cleaned in accordance with routines outlined in makers installation manual.
- Other tests as required by RINA Rules (pressure testing of piping, etc.) and according to maker's manual shall be carried out.
Remarks
1. Installation of the system, spacing of nozzles and components used shall be in accordance with the type examination documentation.
2. Prior to fitting the system on board, the following details shall be submitted to class for approval for each separated case, as minimum:
.1 System arrangement plans including location of nozzles, sections valves, release stations and pump-unit (including water supply);
.2 Documentation of power supply and control system;
.3 Specification of pipes, electrical motor, valves, pumps and associated components;
.4 Pressure drop calculations and water mist capacity calculations;
.5 Arrangement of interface to fire detection and alarm system (where applicable);
.6 Manual with design, installation, operation, test and maintenance instructions.
3. The nozzle shall be marked as para.5 of MSC/Circ.1165 and the Mark of Conformity as per Annex I of 2014/90/EU.