Product Description:
Pressure transmitters suitable for pressure measurement of gases and liquids
OPTIBAR PC5060 VGK54 a b c d e f g h i j k l m n o
OPTIBAR PM5060 VGK64 a b c d e f g h i j k l m n o
Legend:
a= Scope: A, W, F, C or others
b= Approval: M, N, 0, P, 6
c= Process fitting / Material
2-digit alphanumeric code for for TRI-CLAMP, DN or ASME industry type flange with pressure
ratings and any complying with an international standard
d= 1-digit aphanumeric code,
for OPTIBAR PC 5060 sealing concept: Single, Double resp. form seal
for OPTIBAR PM 5060: diaphragm material, fill fluid
e= Process seal / Process temperature:
1-digit alphanumeric code for FKM, EPDM, FFKM -seal for temperatures -40 - 150 °C
(depending on version)
f= Pressure
A Absolute
G Relative
g= Measuring range:
1-digit alphanumeric code for pressure range -1 ... 100.0 bar (-100 ... 10000kPa) or
other national standard units (depending on version)
h= Accuracy class:
H 0.050%/ 0.075%,
E 0.1 %,
S 0.2%
i= Electronics:
Z Two-wire 4 ... 20mA
H Two-wire 4...20mA/HART®
A Two-wire 4...20mA/HART® with SIL - Qualification
S Slave electronics for electronic differential pressure
T Slave electronics for electronic differential pressure with SIL-Qualification
P Profibus PA
j= Supplementary Electronics:
X without ,
Z additional current output
k= Housing:
K Plastic,
A Aluminum,
D Aluminum double chamber,
V Stainless steel (precision casting) 316L,
W Stainless steel double chamber (precision casting),
R Plastic double chamber
l= Housing Version Protection:
D, P, N, M, A, S, K, L, 1
TYPE APPROVAL CERTIFICATE
No. ELE 225024XG
Enclosure - Page 2 of 2
OPTIBAR PC/PM 5060
m= Cable Entry / Connection:
M, S, T, K, U, V, L, 0, D, 6, N, J, 8, P, C, B, F, G, H, W, Z, 1, 7
n= Display/Adjustment module:
X without
A mounted
F without; lid with inspection window
B laterally mounted
K with display/adjustment module with Bluetooth; magnetic pen operation
L laterally mounted; with display/adjustment module with Bluetooth; magnetic pen operation
o= Certificate:
M yes (e.g. FDA; EN 10204-3.1; NACE),
X no (*)
Operating instructions:
- TD_OPTIBAR-PC-5060C_en_201009_4003437403_R03
- TD_OPTIBAR-PM-5060_en_201009_4003437002_R02
- MA_OPTIBAR-PM-5060_en_201012_4003436804_R04
- MA_OPTIBAR-PC-5060_en_201009_4003437205_R05
Test Reports:
- 1-03_BAR80H_F2_1.pdf
- 1-03_BAR80H_F2_2.pdf
- 1-03_BAR80H_F2_3.pdf
- 1-04_BAR82H_F2_1.pdf
- 1-08_BAR80H_F2_1.pdf
- 1-09_BAR80H_F2_1.pdf
- Hermes Hansecontrol Test Report 1401-0027801R01.pdf
- Hermes Hansecontrol Test Report 1401-0027801R02.pdf
- Hermes Hansecontrol Test Report 1401-0027801R03.pdf
- Hermes Hansecontrol Test Report 1401-0160601R01.pdf
- Hermes Hansecontrol Test Report 1401-0160701R01.pdf
- Supplementary Test Reports acc. to IACS E10/ Rev. 7 - 9
- Hermes Hansecontrol Test Reports: 2001-0125101R01/R02/R03/R04/R05
- Paconsult Test Report 14-5756.pdf
- Paconsult Test Report 14-6126.pdf
General Remark:
- It is not allowed to supply OPTIBAR PC/PM series directly from the ship power supply mains.
Such sensors are to be connected to signal conditioning instruments / power supply units with appropriate approval. For any installation in hazardous area suitable safety certificates are to be sent for information and approval.
- Each particular application and installation is to be specifically approved in conjunction with the relevant system in which the components are used.
- The sensing device is to be fitted with a valve or arranged such that it my be isolated and removed without emptying the tank or without impairing the integrity of pressurized system.
- Wireless data communication used for vessel services of category III systems will be specially considered provided the use of the wireless data communication results in an improvement in the safety of the vessel, compared to wired data communication.
|
|