MED189025PUENG- -  -  N-  NKT LKD 4.33 -N- S- S- -27/02/2026- Marine Equipment- - SN- S- - N-  - 1,105,603B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED189025PU- N-Feb 26, 20311105603
 
Form
  Marine Equipment(TO)
Certification N. MED189025PU - (ENG)
Certificate date 27/02/2026
Type Protezione antincendio
Product Fixed water based local application fire fighting systems components for use in category "A" machinery spaces (Nozzles and performance tests)
Item Nº MED/3.48

Model or Denomin.
Items
NKT LKD 4.33
Applicant NK CO., LTD.
Place of requester 194-11 Gwahaksandan-ro, Gangseo-gu  %  46743 Busan  % REPUBLIC OF KOREA
Tel. N.,Fax, Email ---, ---, quality01@nkcf.com
Directive (EU) 2025/1533
Standards IMO MSC.1/Circ.1387
Reference Documents SOLAS 74 Reg.II-2/10, IMO Res.MSC.36(63)-(1994 HSC Code) 7, IMO Res.MSC.97(73)-(2000 HSC Code) 7.
Expire date 26/02/2031
Responsible Office RINA Korea Marine
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Jin Young Kim S

EC TYPE EXAMINATION (MODULE B)
No. MED189025PU

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2025/1533.
MED Item Nº MED/3.48
Description Fixed water based local application fire fighting systems components for use in category "A" machinery spaces (Nozzles and performance tests)
Type NKT LKD 4.33
Applicant NK CO., LTD.
194-11 Gwahaksandan-ro, Gangseo-gu,46743 Busan,REPUBLIC OF KOREA
Testing standards applied IMO MSC.1/Circ.1387
Regulations specified and reference documents SOLAS 74 Reg.II-2/10, IMO Res.MSC.36(63)-(1994 HSC Code) 7, IMO Res.MSC.97(73)-(2000 HSC Code) 7.
Issued in RINA Korea Marine on
This Certificate is valid until
February 27, 2026
February 26, 2031
This Certificate consists of this sheet plus an attachment

________________________________________
Jin Young Kim
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
No.  MED189025PU
Page 1 of 4

Product Description


'Fixed Water Based Local Application Fire Fighting System' manufactured by NK Co., Ltd. is local application water mist system for use in category A machinery spaces, composed of nozzles (spray heads), steel piping, manual or automatic section valves, strainer, control panel and water supply pump(s).

Only the nozzles (Type: NKT LKD 4.33) are type approved by this certificate. Pumps, pipes, valves, couplings and other systems components are subject to case-by-case approval.

The nozzles are to be installed above the protected objects according to the following specifications:

Vertically downward position
Max. horizontal spacing 4.0 m
Min. vertical distance from object 0.5 m
Max. vertical distance from object 14.5 m
Min. operation pressure 12 bar
Flow rate 15 L/min
k-factor (using Q = k x p½): 4.33
Inclined position at an angle of 15° to a vertical direction
Max. horizontal spacing 4.0 m
Min. vertical distance from object 1.0 m
Max. vertical distance from object 6.0 m
Min. operation pressure 12 bar
Flow rate 15 L/min
k-factor (using Q = k x p½): 4.33








ATTACHMENT TO
CERTIFICATE No. MED189025PU
Page 2 of 4
Product Description (Continued)
Inclined position at an angle of 60° to a vertical direction
Max. horizontal spacing 4.0 m
Min. vertical distance from object 1.0 m
Max. vertical distance from object 6.0 m
Min. operation pressure 12 bar
Flow rate 15 L/min
k-factor (using Q = k x p½): 4.33

Shifted distance of the protected area in accordance with vertical distance from object
Vertical distance from object
1 m
2 m
3 m
4 m
5 m
6 m
Shifted distance of the protected area at an angle of 15°
0.65 m
0.755 m
0.825 m
0.895 m
0.96 m
1.00 m
Shifted distance of the protected area at an angle of 60°
1.85 m
2.195 m
2.415 m
2.65 m
2.885 m
3.00 m


ATTACHMENT TO
CERTIFICATE No. MED189025PU
Page 3 of 4
Technical Documentation
  • Technical drawings and Manual, filed by RINA listed on Letter No. PUFP/2026/98/YK008.

Tests Carried Out
  • Test report of Performance Test of a Fixed Water-Based Local Application Fire Extinguishing System (Ref. No. P2010033526), issued by Korea Institute of Machinery and Materials dated on 22-11-2010, filed by RINA with No. PUFP-8325.
  • Test report of Performance Test of a Fixed Water-Based Local Application Fire Extinguishing System (Ref. No. P2011002526), issued by Korea Institute of Machinery and Materials dated on 10-01-2011, filed by RINA with No. PUFP-8326.
  • Test report of Nozzle Clogging Test of a Fixed Water-Based Local Application Fire Extinguishing System (Ref. No. 2011246526), issued by Korea Institute of Machinery and Materials dated on 07-07-2011, filed by RINA with No. PUFP-8322.
  • Test report of Performance Test of a Water Mist Nozzle (Ref. No. 2012103343), issued by Korea Institute of Machinery and Materials dated on 14-03-2012, filed by RINA with No. PUFP-8324.
  • Test report of Nozzle Clogging Test of a Fixed Water-Based Local Application Fire Extinguishing System (Ref. No. KIMM-16-0697), issued by Korea Institute of Machinery and Materials dated on 13-07-2016, filed by RINA with No. PUFP-8323.

Application/Limitation
  • Instruction for installation, use and maintenance are to be available in the ship's official languages.
  • The onboard arrangements, installation of this equipment and other system components are to be evaluated in each case, to the satisfaction of the classification society on board or the flag administration.
  • The system should be suitably designed to withstand ambient temperature changes, vibration, humidity, shock, impact, clogging, and corrosion normally encountered in machinery spaces.
  • The outer nozzles are to be located either at the edge of the protected area or outside the protected area.
  • For a single row of nozzles, the outer nozzles should be placed at least at the edge of the protected area.
  • For individual nozzles or a single row of nozzles, the effective nozzle coverage (width and length) is defined as 1/2 the maximum nozzle spacing

Note
  • None.




ATTACHMENT TO
No. MED189025PU
Pages 4 of 4
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Jin Young Kim