Fixed water-based local application fire fighting system for use in machinery spaces of category A.
Pump unit, piping, section control valves, nozzles, control and monitoring system are described in the Technical Documentation Booklet edit by EUSEBI IMPIANTI.
Technical characteristics
Nozzle type: water mist open nozzles designated as EI-FOG 2IXX1.615 and EI-FOG 2IXX1.915.
("2" as open nozzle - "I" as inox material - "XX" last two digit of year of production - "1.6 or 1.9 " K-Factor - "15" as per 115°, angle of nozzle body)
| Nozzle performances |
| EI-FOG 2IXX1.615 | EI-FOG 2IXX1.915 |
| K-factor (lpm/bar1/2) | 1.6 | 1.9 |
| Nominal operating pressure | 100 bar | 100 bar |
| Minimum vertical distance to fire source | 1.0 m | 1.0 m |
| Maximum vertical distance to fire source | 5.7 m | 3.10 m |
| Nozzle spacing | 3.0 m | 3.0 m |
| Nozzle arrangement (*) | 3x3 grid | 3x3 grid |
| Lateral distance from hazard (**) | 0.75m | 0.75m |
(*) According to Par. 3.4.2.1 and Fig. 3.4.2.5 of Appendix toMSC.1/Circ.1387
(**)The outer nozzles should be installed outside of the protected area at a distance of at least 1/4 of the maximum nozzle spacing.
Single row installation: the outer nozzle should be placed outside the protected area at a distance of at least 1/4 of the maximum nozzle spacing.Reference documents
- Installation, operation and maintenance manual - Local Application System, edit by EUSEBI IMPIANTI and filed by RINA with n° CSST-9396.
- Clogging test reports n° 149/C dated 23/05/2006, edit by TE.S.I Laboratory and filed by RINA with n° FPE-9928.
- Component test report n° E246487 edit by Underwriters Laboratory Inc. on 9/05/2006 and filed by RINA with n° CSST-9397.
- Fire test report n° P301978A dated 04/07/2003 edit by SP Swedish National Testing and Research Institute and filed by RINA with n° FPE 9930.
- Fire test report n° 214/C edit by TE.S.I Srl and filed by RINA with n° CSST-9398.
- Nozzles Heads Type EI-Fog 2Ixx1.1615 and EI-Fog 2Ixx1.1915 issued by EUSEBI IMPIANTI and approved by Rina with n°CSST-14709.