The FTCM Series Nozzles are non-automatic nozzles with open spray head made of Brass or Stainless Steel used in Fixed Water-based Fire-fighting Systems which is designed in accordance with the "Principal Requirements" of IMO MSC.1/Circ.1430, Rev.2, for prescriptive-based system, the system consists of nozzles and section valves in addition to pump unit(s), steel piping, control system as associated equipment.
Only the nozzles are type approved by this certificate. Pumps, pipes, couplings, valves and other systems components are subject to case-by-case approval.
The nozzles were designed with the following types and main characteristics:
Nozzle
Types | K
Factor | Working Pressure | Spray
Angle | Connection
(Male Thread) |
Min. (bar) | Max. (bar) |
FTCM-K-19 | 19 | 1.4 | 10.0 | 60°
80°
100°
120°
140°
160° | BSPT1/2"
(Nozzle thread can be customized to NPT1/2") |
FTCM-K-27 | 27 |
FTCM-K-33 | 33 |
FTCM-K-42 | 42 |
FTCM-K-61 | 61 |
FTCM-K-80 | 80 |
FTCM-K-98 | 98 |
FTCM-K-109 | 109 |
FTCM-K-120 | 120 |
The flow rate and flow profile refer to the nozzle datasheet.
The nozzles are to be installed in a downward position. |
Fields of Application/Limitation
Nozzles are designed/approved for directional spray applications only used in Fixed Water-based Fire-fighting Systems for Ro-Ro Spaces, Vehicle Spaces and Special Category Spaces.
System design and installation shall be in accordance with principal requirements and prescriptive-based system requirements of IMO MSC.1/Circ.1430, Revision 2, Ch.3 and 4. In addition, uniform distribution of nozzles inside protected space as well as overlap of the spray pattern shall be ensured.
 | ATTACHMENT TO
CERTIFICATE No. MED260822WS
Page 2 of 4 |
Continued:
Reference Documents
Technical drawings, datasheet edit by Shanghai Firetec Mechatronic Engineering Co.,Ltd as folloiwing:
1. Technical drawing for FTCM Nozzles approved by RINA with No.: SHFP-23328;
2. Technical datasheet for FTCM Nozzles approved by RINA with No.: SHFP-23329;
3. Typical system calculation for deluge fire-fighting system approved by RINA with No.: SHFP-22963.
Production and Tests Carried Out
The tests for the Nozzles had been carried out in accordance with IMO MSC/Circ.1165:
1. Visual Examination Test Report carried out by Shanghai Firetec Mechatronic Engineering Co.,Ltd dated on July.31 2022, and filed by RINA with No.: SHFP-23437;
2. Functional Test Report carried out by Shanghai Firetec Mechatronic Engineering Co.,Ltd dated on July.25 2022, and filed by RINA with No.: SHFP-23438;
3. Flow Test Report carried out by Shanghai Firetec Mechatronic Engineering Co.,Ltd dated on July.26 2022, and filed by RINA with No.: SHFP-23428;
4. Stress Corrosion Test Report (Ref. No.: WX220520-026-01) for Brass Nozzles carried out by Wuxi RELLAB Testing Service Co., Ltd dated on August.11 2022, and filed by RINA with No.: SHFP-23429;
5. Stress Corrosion Cracking Test Report (Ref. No.: FCT220923-01) for Stainless Steel Nozzles carried out by Shanghai Firetec Mechatronic Engineering Co.,Ltd dated on September.23 2022, and filed by RINA with No.: SHFP-23430;
6. Sulphur Dioxide Corrosion Test Report (Ref. No.: FTC220913-01) carried out by Shanghai Firetec Mechatronic Engineering Co.,Ltd dated on September.13 2022, and filed by RINA with No.: SHFP-23431;
7. Salt Spray Corrosion Test Report (Ref. No.: WX220520-026-02-G1) carried out by Wuxi RELLAB Testing Service Co., Ltd dated on August.24 2022, and filed by RINA with No.: SHFP-23432;
8. Moist Air Exposure Test Report(Ref. No.: FTC220913-09) carried out by Shanghai Firetec Mechatronic Engineering Co.,Ltd dated on April.20 2023, and filed by RINA with No.: SHFP-23433;
9. Heat-resistance Test Report (Ref. No.: WX220520-026-03) carried out by Wuxi RELLAB Testing Service Co., Ltd dated on August.11 2022, and filed by RINA with No.: SHFP-23434;
10. Vibration Test Report carried out by Shanghai Firetec Mechatronic Engineering Co.,Ltd dated on July.29 2022, and filed by RINA with No.: SHFP-23435;
11. Impact Test Report (Ref. No.: WX220520-026-04) carried out by Wuxi RELLAB Testing Service Co., Ltd dated on August.11 2022, and filed by RINA with No.: SHFP-23436.
Installation Testing
The installation tests are to be carried out as following:
1. System shall be cleaned as per the routines outlined in maker’s system description manual.
2. For deluge system, it should be tested for the simultaneous activation of the at least two(2) adjacent sections with full flow through the nozzles at the minimum water discharge density.
3. Testing of manual and remote release of all section valves (without water accepted).
4. Testing of manual and remote start of pumps.
5. Testing of the alarms at the manned control stations.
6. Other tests as required by Class Rules (pressure testing of piping, etc.) or a similar standard acceptable to the Flag Administration and according to maker's manual shall be carried out.
 | ATTACHMENT TO
CERTIFICATE No. MED260822WS
Page 3 of 4 |
Continued:
Marking of the Product
The Nozzles shall be marked with the name of the manufacturer and the type designation as indicated in this certificate.
Remarks
1. Installation of the of nozzles shall be in accordance with the type approval documentation.
2. Prior to fitting the system on board, the following details shall be submitted for approval for each separated case:- Schematic arrangement of the system of jointing nozzles type, sections valves, release stations and pump units, etc.;
- Electrical wiring system including power supply system and system control system;
- System dimensioning and hydraulic calculations;
- Specifications of Pumps, pipes, couplings, valves and other systems components;
- Design, installation, operation and maintenance manual.