Product Description
RT thermostats incorporate a temperature controlled, single pole change over switch where the contact position depends on the temperature of the sensor and the set scale value.
The RT series consists of thermostats with room sensors, duct sensors and capillary tube sensors for general industrial and marine applications.
Main characteristics:
Ambient temperature: -50°C ... +70°C
Contact system: Single-pole changeover switch (SPDT)
Contact load: Alternating cur. AC1=10 A, 400 V / AC3=4 A, 400 V / AC15=3 A, 400 V / Direct cur. DC13: 12 W, 220 V control current
Cable entry: 2 PG 13.5 for 6 – 14 mm diameter cables
Enclosure: IP54 / IP66
Thermostat Type RT With Cylindrical Remote Sensor:
Type | Setting Charge | Adjustable Differential Range | At Highest Range Setting | Type of Charge* | Capillary tube L. |
At lowest range setting | At highest range setting |
RT9 | -45 - -15°C | 2.2 - 10°C | 1 – 4.5°C | 150°C | A | 2m |
RT13 | -30 - 0°C | 1.5 - 6°C | 1 - 3°C | 150°C | A | 2m |
RT3 | -25 - 15°C | 2.8 - 10°C | 1 – 4°C | 150°C | A | 2m |
RT3 | -25 - 15°C | 2.8 - 10°C | 1 – 4°C | 150°C | A | 5m |
RT3 | -25 - 15°C | 2.8 - 10°C | 1 – 4°C | 150°C | A | 8m |
RT2 | -25 - 15°C | 5 - 18°C | 6 - 20°C | 150°C | B | 2m |
RT7 | -25 - 15°C | 2 - 10°C | 2.5 – 14°C | 150°C | B | 2m |
RT7 | -25 - 15°C | 2 - 10°C | 2.5 – 14°C | 150°C | B | 5m |
RT7 | -25 - 15°C | 2 - 10°C | 2.5 – 14°C | 150°C | B | 8m |
RT8 | -20 - 12°C | 1.5 - 7°C | 1.5 - 7°C | 145°C | B | 2m |
RT12 | -5 - 10°C | 1 – 3.5°C | 1 – 3°C | 65°C | B | 2m |
RT14 | -5 - 30°C | 2 - 8°C | 2 - 10°C | 150°C | B | 2m |
RT14 | -5 - 30°C | 2 - 8°C | 2 - 10°C | 150°C | B | 3m |
RT14 | -5 - 30°C | 2 - 8°C | 2 - 10°C | 150°C | B | 5m |
RT14 | -5 - 30°C | 2 - 8°C | 2 - 10°C | 150°C | B | 8m |
RT14 | -5 - 30°C | 2 - 8°C | 2 - 10°C | 150°C | B | 10m |
RT26 | -5 - 50°C | 2 - 9°C | 3 – 19°C | 150°C | B | 2m |
RT23 | 5 - 22°C | 1.1 - 3°C | 1 - 3°C | 85°C | B | 2m |
RT15 | 8 - 32°C | 1.6 - 8°C | 1.6 – 8°C | 150°C | B | 2m |
RT101 | 25 - 90°C | 2.4 - 10°C | 3.5 - 20°C | 300°C | B | 2m |
RT101 | 25 - 90°C | 2.4 - 10°C | 3.5 - 20°C | 300°C | B | 3m |
RT101 | 25 - 90°C | 2.4 - 10°C | 3.5 - 20°C | 300°C | B | 5m |
RT101 | 25 - 90°C | 2.4 - 10°C | 3.5 - 20°C | 300°C | B | 8m |
RT101 | 25 - 90°C | 2.4 - 10°C | 3.5 - 20°C | 300°C | B | 10m |
RT106 | 20 - 90°C | 4 - 20°C | 2 - 7°C | 120°C | C | 2m |
RT106 | 20 - 90°C | 4 - 20°C | 2 - 7°C | 120°C | C | 3m |
RT106 | 20 - 90°C | 4 - 20°C | 2 - 7°C | 120°C | C | 5m |
RT108 | 30 - 140°C | 5 - 20°C | 4 - 14°C | 220°C | B | 2m |
RT107 | 70 - 150°C | 6 - 25°C | 1.8 - 8°C | 215°C | C | 2m |
RT107 | 70 - 150°C | 6 - 25°C | 1.8 - 8°C | 215°C | C | 3m |
RT107 | 70 - 150°C | 6 - 25°C | 1.8 - 8°C | 215°C | C | 5m |
RT107 | 70 - 150°C | 6 - 25°C | 1.8 - 8°C | 215°C | C | 8m |
RT107 | 70 - 150°C | 6 - 25°C | 1.8 - 8°C | 215°C | C | 10m |
RT120 | 120 - 215°C | 7 - 30°C | 1.8 - 9°C | 260°C | C | 2m |
RT120 | 120 - 215°C | 7 - 30°C | 1.8 - 9°C | 260°C | C | 5m |
RT120 | 120 - 215°C | 7 - 30°C | 1.8 - 9°C | 260°C | C | 8m |
RT123 | 150 - 250°C | 6.5 - 30°C | 1.8 - 9°C | 300°C | C | 2m |
RT123 | 150 - 250°C | 6.5 - 30°C | 1.8 - 9°C | 300°C | C | 5m |
RT124 | 200 - 300°C | 5 - 25°C | 2.5 - 10°C | 350°C | C | 2m |
RT124 | 200 - 300°C | 5 - 25°C | 2.5 - 10°C | 350°C | C | 5m |
Thermostat Type RT With room sensor, duct sensor and capillary tube sensor:
Type | Setting Range | Adjustable Differential Range | Max. Sensor Temp. | Type of Charge* | Capillary tube L. | Sensor Type |
At lowest range setting | At highest range setting |
RT17 | -50 - -15°C | 2.2 - 7°C | 1.5 – 5°C | 100°C | A | - | 1 |
RT11 | -30 - 0°C | 1.5 - 6°C | 1 - 3°C | 66°C | A | - | 1 |
RT34 | -25 - 15°C | 2 - 10°C | 1 – 4°C | 100°C | B | - | 1 |
RT4 | -5 - 30°C | 1.5 - 7°C | 1 – 4°C | 75°C | A | - | 1 |
RT115 | 10 - 35°C | - | - | 92°C | B | - | 1 |
RT103 | 10 - 45°C | 1.3 - 7°C | 2.5 – 14°C | 100°C | A | - | 1 |
RT140 | 15 - 45°C | 1.8 - 8°C | 2.5 – 14°C | 240°C | B | 2m | 2 |
RT141 | 40 - 80°C | 1.9 - 9°C | 1.5 - 7°C | 250°C | B | 2m | 2 |
RT102 | 25 - 90°C | 2.4 – 10°C | 1 – 3°C | 300°C | B | 2m | 3 |
Thermostat Type RT With adjustable neutral zone:
Type | Setting Range | Mechanical Diff. | Adjustable Differential Range | Max. Sensor Temp. | Type of Charge* | Capillary tube L. | Sensor Type |
At lowest range setting | At highest range setting |
RT 8L | -20 - 12°C | 1.5°C | 1.5 – 4.4°C | 1.5 – 4.9°C | 145°C | B | 2 | 4 |
RT 14L | -5 - 30°C | 1.5°C | 1.5 - 5°C | 1.5 - 5°C | 150°C | B | 2 | 4 |
RT 16L | 0 - 38°C | 1.5/0.7°C | 1.5 - 5°C | 0.7 – 1.9°C | 100°C | A | - | 1 |
RT 140L | 15 - 45°C | 1.8/2°C | 1.8 – 4.5°C | 2 – 5°C | 240°C | B | 2 | 2 |
RT 101L | 25 - 90°C | 2.5/3.5°C | 2.5 - 7°C | 3.5 – 12.5°C | 300°C | B | 2 | 4 |
Differential Temperature Switch Type RT 270:
Setting: 0 - 15°C; mechanical diff, 2°C; operating range – 30 - 140°C; Max temp. 65°C.
*Note: Types of Charge:
A: Vapour Charge – sensor must not be the warmest part
B: Adsorption Charge
C: Partial Charge – the sensor must not be the coldest part
Documents:
Product Specification Document of RT - AI245286497322en-000301 dated 2021.03
Product Specification Document of Differential Temp. Switch Datasheet - AI240786443892en-000901 dated 2017.09
Declaration of Conformity dated 12.06.2025
This certificate replaces the previous certificate ELE086320XG/004