ELE239126XGENG- -  -  N- Series CAS -N- S- S- -08/07/2026- Prodotti Elettrici- - SN- N- - N-  - 875,550BbisProdotti ElettriciNumero Pratica,NumDich,Norma,NumBusta,Richiesta,Validità- ELE239126XG- N-Jul 7, 2031875550
 
Form
  Prodotti Elettrici(TO)
Certification N. ELE239126XG - (ENG)
Certificate date 08/07/2026
Type Impianti di Automazione
Product Pressostati e Termostati

Model or Denomin.
Items
Series CAS
Applicant DANFOSS A/S
Place of requester Nordborgvej 81% DK-6430 Nordborg %DENMARK
Tel. N.,Fax, Email 0045 7488 3404, 0045 74884000, Flemming_boss@danfoss.com
Standards RINA Rules for the Classification of Ships - Part C- Machinery, Systems and Fire Protection - Ch.3 , Sect. 8, Table 1
Expire date 07/07/2031
Head Office HAMBURG
Interrut.senza Dettaglio ENG
Vuoto Querysave
S
TYPE APPROVAL CERTIFICATE
No. ELE239126XG
This is to certify that the product below is found to be in compliance with the applicable requirement of the RINA type approval system.

Description Pressure switch and thermostat
Type Series CAS
Applicant DANFOSS A/S
Nordborgvej 81
DK-6430 Nordborg
DENMARK
Reference standards RINA Rules for the Classification of Ships - Part C- Machinery, Systems and Fire Protection - Ch.3 , Sect. 8, Table 1
  

 
 
   .   This Certificate is valid until July 7, 2031
_________________________________
RINA Services S.p.A.
Cinar Kutlar
This certificate consists of this page and 1 enclosure
**** NOTICE: This is NOT an official certificate ****

TYPE APPROVAL CERTIFICATE
No. ELE239126XG
Enclosure Page 1 of 2
Series CAS
Product Description

The CAS series consists of a series of pressure-controlled switches and temperature-controlled switches. This series meets demands for a high level of enclosure, robust and compact construction and resistance to shock and vibration.


The series is suitable for use in alarm and regulation systems in factories, diesel plants, compressors, power stations and on-board ships.

Main characteristics of Pressure Switches CAS 133 - 139

Ambient temperature: -40°C - 70°C


Temperature of medium: -40°C - 100°C
Cable entry: Cable diameters from 5 – 14 mm
Vibration resistance: Vibration-stable in the range 2 – 30 Hz amplitude 1.1 mm and 30 – 100 Hz, 4 g
Contact load: Alternating current AC-14 / AC-15: 0.1 A, 220 V, Direct current DC-13: 12 W, 125 V
Enclosure: IP67

Main characteristics of Pressure Switches CAS 143 - 155

Ambient temperature: -25°C - 70°C


Temperature of medium: -25°C - 100°C
Cable entry: Cable diameters from 5 – 14 mm
Vibration resistance: Vibration-stable in the range 2 – 30 Hz amplitude 1.1 mm and 30 – 100 Hz, 4 g
Contact load: Alternating current AC-14 / AC-15: 0.1 A, 220 V, Direct current DC-13: 12 W, 125 V
Enclosure: IP67

Main characteristics of Thermostat

Ambient temperature: -25°C - 70°C


Switch: CAS 178, CAS 180, Cas 181: Microswitch with single pole changeover (SPDT)
CAS 1080: Microswitch with single pole changeover (2 x SPDT)
Cable entry: CAS 178, CAS 180, Cas 181: Pg 13.5 for cable diameters from 5 – 14 mm
CAS 1080: 2 x g 13.5 for cable diameters from 5 – 14 mm
Vibration resistance: Vibration-stable in the range 2 – 30 Hz amplitude 1.1 mm and 30 – 100 Hz, 4 g
Contact load: Alternating current AC-14 / AC-15: 0.1 A, 220 V, Direct current DC-13: 12 W, 125 V
Enclosure: IP67

Standard Pressure Switches:

Type
Setting Range
Mechanical Differential
Permissible Operating Pressure
Max. Test Pressure
Min. Burst Pressure
Pressure Connection
CAS 133
0 – 3.5bar
0.1bar
10bar
10bar
40bar
G1/4
CAS 136
0 – 10bar
0.2bar
22bar
22bar
40bar
G1/4
CAS 137
6 – 18bar
0.3bar
27bar
27bar
72bar
G1/4
CAS 139
10 – 35bar
0.6bar
53bar
53bar
100bar
G1/4


Pressure Switches for High Pressure and Strongly Pulsating Media:

Type
Setting Range
Mechanical Differential
Permissible Operating Pressure
Max. Test Pressure
Min. Burst Pressure
Pressure Connection
CAS 143
1 – 10bar
0.2 – 0.6bar
120bar
180bar
240bar
G1/4
CAS 145
4 – 40bar
0.8 – 2.4bar
120bar
180bar
240bar
G1/4
CAS 147
6 – 60bar
1 – 3bar
120bar
180bar
240bar
G1/4

Differential Pressure Switch:



Type
Setting Range
Mechanical Differential
Permissible Operating Pressure
Max. Test Pressure
Min. Burst Pressure
Pressure Connection
CAS 155
0.2 – 2.5bar
0.1bar
0 – 8bar
22bar
42bar
2 x G1/4

Thermostat, type CAS 178 – CAS 181:



Type
Setting Range
Mech. Diff. Adj./Fixed
Max. Sensor Temp
Suitable Sensor Length (mm)
Cap. Tube Length
CAS 178
20 – 80°C
2.0°C
130°C
65
75
110
160
2m
CAS 180
70 – 120°C
2.0°C
220°C
65
75
110
160
2m
CAS 181
60 – 150°C
2.0°C
250°C
65
75
110
160
2m

2-step Thermostat, type CAS 1080:



Type
Factory Setting
Mechanical Differential
Max. Temperature
Insert Sensor Length
Step 1
Step 2
CAS 1080
80°C
80°C
2.0°C
220°C
200mm

Documents:

Data Sheet of Pressure Switch and Thermostat Type CAS - AI556241553702en-000101 dated 2026.03


Declaration of Conformity dated 25.05.2026

This certificate replaces the previous certificate ELE057221XP.

HAMBURG July 08, 2026
**** NOTICE: This is NOT an official certificate ****