MED274624CSENGD- -  -  N- MD 2020 -N- S- S- -09/09/2024- Marine Equipment- - SN- S- - N-  - 840,487B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità,EmailR- MED274624CS- N-Sep 8, 2029840487
 
Form
  Marine Equipment(TO)
MED068924SP/002
Certification N. MED274624CS - (ENG)
Certificate date 09/09/2024
Description
Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces,(a) Control and indicating equipment,(b) Power supply equipment
Type Protezione antincendio
Product Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces: (a) Control and indicating equipment
Item Nº MED/3.51a,MED/3.51b

Model
Items/Sizes
MD 2020
Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
Place of requester VIA GRETI DEL VARA 9  %  19020 Follo (SP)  % ITALY
Tel. N.,Fax, Email 0187 599101, 0187 558983, d.dido@microdatasrl.it
Directive (EU) 2024/1975
Standard EN 54-2:1997 incl. AC:1999 and A1:2006,EN 54-4:1997 incl. AC:1999, A1:2002 and A2:2006,IEC 60092-504:2016,IEC 60533:2015,Type Test IACS UR E10,EN IEC 62923-1:2018,EN IEC 62923-2:2018,IEC 60945(2002) incl. Corr.1(2008)
Reference Documents SOLAS '74 Reg. II-2/7,SOLAS 74 Reg. X/3,IMO Res. MSC.36(63)-(1994 HSC Code) 7,IMO Res. MSC.97(73)-(2000 HSC code)7,IMO Res.MSC.98(73)-(FSS Code)9,IMO Res. MSC.302(87),IMO Res.MSC.391(95)-(IGF code) 11,IMO Res. MSC.1/Circ 1487,IMO MSC.1/Circ 1242,IMO MSC.1/Circ 1528,IMO MSC.1/Circ 1554,RINA Rules for the certification of Marine Equipment
Validity 08/09/2029
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Claudio Langella S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED274624CS

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2023/1667.
MED Item Nº MED/3.51a,MED/3.51b
Description Fixed fire detection and fire alarm systems components for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces,(a) Control and indicating equipment,(b) Power supply equipment
Type MD 2020
Applicant MICRODATA DUE - SOCIETA' A RESPONSABILITA' LIMITATA
VIA GRETI DEL VARA 9,19020 Follo (SP),ITALY
Testing standards EN 54-2:1997 incl. AC:1999 and A1:2006,EN 54-4:1997 incl. AC:1999, A1:2002 and A2:2006,IEC 60092-504:2016,IEC 60533:2015,Type Test IACS UR E10,EN IEC 62923-1:2018,EN IEC 62923-2:2018,IEC 60945(2002) incl. Corr.1(2008)
Reference standards SOLAS '74 Reg. II-2/7; SOLAS 74 Reg. X/3; IMO Res. MSC.36(63)-(1994 HSC Code) 7; IMO Res. MSC.97(73)-(2000 HSC code)7; IMO Res.MSC.98(73)-(FSS Code)9; IMO Res. MSC.302(87); IMO Res.MSC.391(95)-(IGF code) 11; IMO Res. MSC.1/Circ 1487; IMO MSC.1/Circ 1242; IMO MSC.1/Circ 1528; IMO MSC.1/Circ 1554; RINA Rules for the certification of Marine Equipment
Issued in Genoa on
This Certificate is valid until
September 9, 2024
September 8, 2029
This Certificate consists of this sheet plus an attachment

________________________________________
Luigi Benedetti
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED274624CS
Page 1 of 3
Product description:
Analogue and addressable Fire detection and fire alarm system consisting of:

Fire alarm control panel
MD2020-CU (P/N-30103)
Power supply module
MD2020-PSU (P/N-30378)
Interface Module
MD2020-CTB (P/N-30377)
Branch control unit
MD2020-BCU (P/N-30287)
Loop control unit
MD2020-LCU (P/N-30284)
Remote node
MD2020-RN (P/N-30513)

Fire Alarm Central Unit is able to work in the following configurations:
a) for the management of Centralized Systems (Only one Central Unit) or distributed system
(several central unit net connected) ; detectors are connected in a Loop configuration.
b) for the management of Distributed System, detectors are connected on open electric lines
named Branch

Main features:


Up to 40 detection Branches/Loops are managed through Branch control Unit BCU and Loop Control Unit LCU card.
An additional 40 units can be added using MD2020-RN.
Up to 127 devices may be connected to each Loop
Up to 180 devices may be connected to each Branch
The central units are able to detect any fault occurring on the system (eg. Loop/ Branch cable break, detector failure, etc.)
The central units provides the following additional functions:
- Alarm, Failure, Delayed alarm, System, Alarm sounder, Failure Sounder relay
The MD2020-CU can be connected to the Alarm Repeater Unit MD9860

The MD2020-CTB also implements additional Input/Output features. These extra I/O capabilities are managed by the CTB's internal microprocessor, which communicates with the CU via a dedicated serial line:

- n° 18 programmable outputs – 4 relay / 14 static
- n° 04 monitored inputs – 2 isolated / 2 non isolated
- n° 01 thermistor input – for connecting external thermistor

Microdata Due Software description:
doc. n. D44507 Rev. 0: Fire Alarm Central Unit MD2020-CU Software Requirements (08/01/2022)
doc. n. IRS 40109 Rev. L: Fire Alarm Central Unit MD2020-CU External Communication Interface Specification

Microdata Due Reference documents:
Technical specificatio: n doc. n. ST44513 Rev. 0 (04/09/2023)
User Manual: D44490 Rev. 0 (02/05/2024) ;
Layout: 30148-16; 52933_1; 30039-02, 30410-02, 30412-02, 30288-02, 30285-02, 30375-02;
Risk Assessment: doc. D44517 rev. 0 (22/04/2024)
FMEA Microdata Due doc. n. D42343 Rev. 0 (13/05/2024)
doc. n.ST 43415 Rev. 0: Fire Alarm Central Unit MD2020-CU Technical Specification (04/09/2023)
doc. n.D 43427 Rev. A: Fire Alarm Central Unit MD2020-CU - Data Sheet







ATTACHMENT TO
CERTIFICATE No. MED274624CS
Page 2 of 3

Test reports :
Doc. Microdata Due IS44476 rev.C, Annex A, B, C, and D(Conformity to EN 54-2, EN 54-4 and FSS code as amended., RINA Rules part C, Ch, 3, Sec. 3, EN IEC 62923-1:2018, EN IEC 62923-2:2018)
Microdata Due IS 43423 Demo for Rina Certification (02/05/2024)
TesLab/ Environmental report doc. n.245168N-a (31/05/24)
TesLab/ Environmental report doc. n.245168N-b (31/05/24)
TesLab/ Environmental report doc. n.243078F-a (15/05/24)
TesLab/ Environmental report doc. n.243078F-b (15/05/24)



The complete sets of documents related to:
- Software
- Demo System for Environmental and functional Tests
- General Specification about MD2020 CU (Control Unit), PSU (Power Supply Unit),
BCU (Branch Control Unit), LCU (Loop Control Unit), CTB (Control Terminal Board),
RN (Remote Node)

have been archived in the Leonardo Draw Plus portal under the project:
https://leodrawplus.rina.org/projects/50876/detail

Reference documents
MED-APP dated 26/10/2023.
Offer N° 2024/16581 dated 06/06/2024




ATTACHMENT TO
CERTIFICATE No. MED274624CS
Pages 3 of 3
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Luigi Benedetti
**** NOTICE: This is NOT an official certificate ****