Form
  Marine Equipment(TO)
MED232323WS
Certification N. MED160923WS - (ENG)
Certificate date 13/10/2023
Type Protezione antincendio
Product Fixed water based local application fire fighting systems components for use in category "A" machinery spaces (Nozzles and performance tests)
Item Nº MED/3.48

Model or Denomin.
Items
FWLF-MP
Applicant GSI MARINE RESEARCH CENTER
Place of requester Room 1408, No.37 Jinlong Road, Nansha Street, Nansha District Guangzhou (Guangdong)  % CHINA
Tel. N.,Fax, Email 18102781687, ---, jszx.kcs.yfs@chinagsi.com
Directive (EU) 2023/1667
Standards IMO MSC.1/Circ.1387
Reference Documents SOLAS 74 Reg. II-2/10, IMO Res.MSC.36(63)-(1994 HSC Code) 7, IMO Res.MSC.97(73)-(2000 HSC Code) 7.
Request 2023/04/11
Expire date 12/10/2028
Head Office SHANGHAI
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Qiang Sun S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED160923WS

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2023/1667.
MED Item Nº MED/3.48
Description Fixed water based local application fire fighting systems components for use in category "A" machinery spaces (Nozzles and performance tests)
Type FWLF-MP
Applicant GSI MARINE RESEARCH CENTER
Room 1408, No.37 Jinlong Road, Nansha Street, Nansha District Guangzhou (Guangdong),CHINA
Testing standards IMO MSC.1/Circ.1387
Reference standards SOLAS 74 Reg. II-2/10, IMO Res.MSC.36(63)-(1994 HSC Code) 7, IMO Res.MSC.97(73)-(2000 HSC Code) 7.
Issued in SHANGHAI on
This Certificate is valid until
October 13, 2023
October 12, 2028
This Certificate consists of this sheet plus an attachment

________________________________________
Qiang Sun
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED160923WS
Page 1 of 4

Product Description


The system (Type: FWLF-MP) is a water mist system for use in protection of Machinery Spaces of Category A or similar fire risk areas, composed of nozzles (spray heads), steel piping, manual or automatic section valves, test valves, control panel and water supply pump(s).

The system is to be designed according to principal requirements for the system, SOLAS '74 Reg.II-2/10.5.6 and IMO MSC.1/Circ.1387.

Only the nozzles are with the scope of this MED certificate.


Pumps, pipes, valves, couplings and other systems components are subject to case-by-case approval.

The open type nozzles (type: HKY-2 & HKY-3) made of Stainless steel 316L with the following characteristics:

Product Model
FWLF-MP
Min. working pressure
1.2 MPa
Nozzled Details
Type
HKY-2
HKY-3
K-factor
2.1
5.1
Flow
(using Q = K • (10 • p)1/2)
5.94 L/min at p = 0.8 Mpa
14.4 L/min at p =0.8 Mpa
Spray Angle
100°
80°

Field of Application/Limitation

The nozzles are approved for use in a fixed water-based local application fire-extinguishing system for protection of Machinery Spaces of Category A or similar fire risk areas.


ATTACHMENT TO
CERTIFICATE No. MED160923WS
Page 2 of 4
Continued:

The nozzles are to be installed above the protected objects according to the following specifications:

Items
For heights between 0.5 and 5.0 m*
For heights between 4.8 and 12.0 m*
Nozzle type
HKY-2
HKY-3
Maximum Horizontal Spacing
2.0 to 2.5 m
3.0 m
Approved height above
protected object
0.5~1.5m (for nozzles spacing 2.0m)
1.5~5.0m (for nozzles spacing 2.5m)
4.8 to 12.0 m
Minimum pressure
p = 0.8 Mpa (at spray heads)
Nozzle Arrangement Form**
1x1, 2x2, 1x3
* Nozzles are to be installed out to a position being at the periphery of the protected object (see IMO MSC/Circ.1387, annex 3.4.2.2).
The nozzles are to be installed in a pendant (downward) position.
** Nozzles in single rows are accepted when half spacing is used, the outer nozzle should be placed at least at
the edge of the protected area.

Reference Documents

Technical documents edited by GSI Marine Research Center as below:
- Typical Technical Documentation for FWBLAFFS approved by RINA with No.: SHFP-24776;
- Bill of Material (For Fixed Water-Based Application Fire-Fighting Installation) filed by RINA with No.: SHFP-24779.

Tests Carried Out

The nozzles were tested according to IMO MSC/Circ.1165 and IMO MSC.1/Circ.1387 as per below:
- Evaluation and Test Report (Ref. No.: NX2023071704) for Nozzles carried out by Nanjing Fire Labratory Technology Co., Ltd, dated on Aug.11.2023, and filed by RINA with No.: SHFP-24780;
- Evaluation and Test Report (Ref. No.: PG018-230243*) for Nozzles carried out by Shanhgai Jianke Technical Assessment of Construction Co., Ltd, dated on Sep.26.2023, and filed by RINA with No.: SHFP-24782;
- Fire Extinguishing Tests according to IMO MSC/Circ.1387, and filed by RINA with No.: SHFP-24766.

Installation Testing

The installation tests of the system as following:
- At least one section should be tested with full flow through the nozzles.
- Test of manual and remote release of all section valves and start of pumps.
- Testing of alarms (SOLAS Ch. II-2, Reg.10.5.6.4).
- Testing of automatic start of system (in case of unattended machinery spaces).
- Pressure testing of water pipe system.
- System to be cleaned in accordance with routines outlined in makers installation manual.
- Other tests as required by RINA Rules (pressure testing of piping, etc.) and according to maker's manual shall be carried out.

Remarks

1. Installation of the system, spacing of nozzles and components used shall be in accordance with the type examination documentation.



ATTACHMENT TO
CERTIFICATE No. MED160923WS
Page 3 of 4
Continued:

2. Prior to fitting the system on board, the following details shall be submitted to class for approval for each separated case, as minimum:


.1 System arrangement plans including location of nozzles, sections valves, release stations and pump-unit (including water supply);
.2 Documentation of power supply and control system;
.3 Specification of pipes, electrical motor, valves, pumps and associated components;
.4 Pressure drop calculations and water mist capacity calculations;
.5 Arrangement of interface to fire detection and alarm system (where applicable);
.6 Manual with design, installation, operation, test and maintenance instructions.
3. The nozzles shall be marked with the name of the producer and the type designation as indicated in this certificate.




ATTACHMENT TO
CERTIFICATE No. MED160923WS
Pages 4 of 4
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 