The system (Type: FWLF-MP) is a water mist system for use in protection of Machinery Spaces of Category A or similar fire risk areas, composed of nozzles (spray heads), steel piping, manual or automatic section valves, test valves, control panel and water supply pump(s).
The system is to be designed according to principal requirements for the system, SOLAS '74 Reg.II-2/10.5.6 and IMO MSC.1/Circ.1387.
Only the nozzles are with the scope of this MED certificate.
Pumps, pipes, valves, couplings and other systems components are subject to case-by-case approval.
The open type nozzles (type: HKY-2 & HKY-3) made of Stainless steel 316L with the following characteristics:
Product Model | FWLF-MP |
Min. working pressure | 1.2 MPa |
Nozzled Details |
Type | HKY-2 | HKY-3 |
K-factor | 2.1 | 5.1 |
Flow
(using Q = K • (10 • p)1/2) | 5.94 L/min at p = 0.8 Mpa | 14.4 L/min at p =0.8 Mpa |
Spray Angle | 100° | 80° |
Field of Application/Limitation
The nozzles are approved for use in a fixed water-based local application fire-extinguishing system for protection of Machinery Spaces of Category A or similar fire risk areas.
 | ATTACHMENT TO
CERTIFICATE No. MED160923WS
Page 2 of 4 |
Continued:
The nozzles are to be installed above the protected objects according to the following specifications:
Items | For heights between 0.5 and 5.0 m* | For heights between 4.8 and 12.0 m* |
Nozzle type | HKY-2 | HKY-3 |
Maximum Horizontal Spacing | 2.0 to 2.5 m | 3.0 m |
Approved height above
protected object | 0.5~1.5m (for nozzles spacing 2.0m)
1.5~5.0m (for nozzles spacing 2.5m) | 4.8 to 12.0 m |
Minimum pressure | p = 0.8 Mpa (at spray heads) |
Nozzle Arrangement Form** | 1x1, 2x2, 1x3 |
* Nozzles are to be installed out to a position being at the periphery of the protected object (see IMO MSC/Circ.1387, annex 3.4.2.2).
The nozzles are to be installed in a pendant (downward) position.
** Nozzles in single rows are accepted when half spacing is used, the outer nozzle should be placed at least at
the edge of the protected area. |
Reference Documents
Technical documents edited by GSI Marine Research Center as below:
- Typical Technical Documentation for FWBLAFFS approved by RINA with No.: SHFP-24776;
- Bill of Material (For Fixed Water-Based Application Fire-Fighting Installation) filed by RINA with No.: SHFP-24779.
Tests Carried Out
The nozzles were tested according to IMO MSC/Circ.1165 and IMO MSC.1/Circ.1387 as per below:
- Evaluation and Test Report (Ref. No.: NX2023071704) for Nozzles carried out by Nanjing Fire Labratory Technology Co., Ltd, dated on Aug.11.2023, and filed by RINA with No.: SHFP-24780;
- Evaluation and Test Report (Ref. No.: PG018-230243*) for Nozzles carried out by Shanhgai Jianke Technical Assessment of Construction Co., Ltd, dated on Sep.26.2023, and filed by RINA with No.: SHFP-24782;
- Fire Extinguishing Tests according to IMO MSC/Circ.1387, and filed by RINA with No.: SHFP-24766.
Installation Testing
The installation tests of the system as following:
- At least one section should be tested with full flow through the nozzles.
- Test of manual and remote release of all section valves and start of pumps.
- Testing of alarms (SOLAS Ch. II-2, Reg.10.5.6.4).
- Testing of automatic start of system (in case of unattended machinery spaces).
- Pressure testing of water pipe system.
- System to be cleaned in accordance with routines outlined in makers installation manual.
- Other tests as required by RINA Rules (pressure testing of piping, etc.) and according to maker's manual shall be carried out.
Remarks
1. Installation of the system, spacing of nozzles and components used shall be in accordance with the type examination documentation.
 | ATTACHMENT TO
CERTIFICATE No. MED160923WS
Page 3 of 4 |
Continued:
2. Prior to fitting the system on board, the following details shall be submitted to class for approval for each separated case, as minimum:
.1 System arrangement plans including location of nozzles, sections valves, release stations and pump-unit (including water supply);
.2 Documentation of power supply and control system;
.3 Specification of pipes, electrical motor, valves, pumps and associated components;
.4 Pressure drop calculations and water mist capacity calculations;
.5 Arrangement of interface to fire detection and alarm system (where applicable);
.6 Manual with design, installation, operation, test and maintenance instructions.
3. The nozzles shall be marked with the name of the producer and the type designation as indicated in this certificate.