Extinguishing Agent:
| Trade name | FK-5-1-12 - CF3CH2C(O)CF(CF3)2 |
| Manufacturer | Any Company with UL or FM FK-5-1-12 approval |
| Minimum design concentration | 5.85 % |
| NOAEL (% volume) | 10.0 |
| LOAEL (% volume) | >10.0 |
| Cylinder capacity | 20, 50, 90, 140, 280, 390, 450, 850 lb or equivalent liters capacity |
| Storage pressure | 25 bars at 21° C (360 Psi at 70° F) |
| Operating temperature | -18° to 55° C (0° to 130° F) |
| Assembly cylinder position | Vertical only |
Discharge nozzle: brass nozzle size (1/2" ÷ 2") 16 Port 360°/ 7 Port 180°- Minimum pressure: 4.87 bar;
Container valves: 1" BSPT/ 2" BSPT /3" Flare - Material: brass CZ122 or UNS36000; Max working pressure: 33.4 bar.
Field of application
Fixed gas fire-extinguishing systems for use in machinery spaces of category A and cargo pump-rooms equivalent to fire-extinguishing systems required by SOLAS Ch II-2, Reg 10.5 and by para 2.2 of Chapter 5 of Fire Safety System Code.
Reference documents
- Marine Novec 1230 System - Design, Installation, Recharge and Maintenance Manual issued on January 30, 2006 by Fireboy-Xintex Marine Safety Systems and filed by RINA with n° CSST 6052.
- Discharge nozzle, size 15÷50mm - Datasheet n° DS01830, issued by Fireboy-Xintex and approved by RINA with n° CSST 12999;
- Container Valve Assembly, 25mm / 50mm / 80mm, datasheet n° DS01102, DS01122 and DS01125 issued by Fireboy-Xintex and approved by RINA with n° CSST 13000, CSST 13001 and CSST 13002.
Test report
Fire Test report n° EX6263 issued by Underwriters Laboratories Inc. on September 23, 2002 and filed by RINA with n° CSST 6053.Remarks
- In case of design concentrations above the NOAEL concentrations, controls as required by para 2.2.2.1 and 2.2.2.2 of Chapter 5 of Fire Safety System Code are to be provided;
- System using only one bottle located inside the protected space, can not be accepted. Such systems shall be designed with the bottle located outside the protected space.