Product Description
Manual call point (addressable type)
Type:J-SAP-1340
Rated Voltage:15-32VDC
Alarm current: ≤3.5mA
Operating temperature: -40℃~70℃
Enclosure Protection class: IP56
Manual call point (conventional type)
Type:J-SAF-1341
Rated Voltage:8.5-32VDC
Alarm current: ≤70mA
Operating temperature: -40℃~70℃
Enclosure Protection class: IP56
Explosion-proof manual call point
Type:J-SAF-1342Ex
Rated Voltage:8.5-28VDC(Power must be supplied through the safe barrier)
Alarm current: ≤93mA
Operating temperature: T5: -40℃~70℃, T6: -40℃~55℃,
Enclosure Protection class:IP56
Explosion-proof mark: Ex ia IIC T5/T6 Ga
Intrinsic Safety parameter: Ui=28V, Ii=93mA, Pi=0.65W, Ci=0, Li=0
 | ATTACHMENT TO
CERTIFICATE No. MED244723WS/004
Page 2 of 3 |
Application
Fixed fire detection and fire alarm systems components, manual call point for control stations, service spaces, accommodation spaces, cabin balconies, machinery spaces and unattended machinery spaces in marine and offshore field.
Design Assessment The design assessment is based on SOLAS 74 Reg. II-2/7, SOLAS 74 Reg. X/3, IMO Res. MSC.36(63)-(1994 HSC Code) 7, IMO Res. MSC.97(73)-(2000 HSC Code) 7, IMO Res. MSC.98(73)-(FSS Code) 9, IMO Res. MSC.391(95)-(IGF Code) 11, IMO MSC.1/Circ.1242.
System components installed in ships, as applicable, comply with IEC standards: IEC 60092-504:2016, IEC 60533:2015.
Tests Carried Out Test reports: “Shanghai Institute of Quality Inspection and Technical Research.". Report No.: W02314100084E. "Shanghai Inspection and Testing Institute of Instruments and Automation System Co., Ltd." Report No.: A23-014-ZC, according to EN 54-11:2001 incl. A1:2005, IEC 60092-504:2016, IEC 60533:2015. Filed by RINA with drawing No. SHEL-17462, and SHEL-xxx.
Inspection report (Date on 2024, February 1) edit by "JIAXING KEXUN ELECTRON CO., LTD. " and signed by RINA Surveyor. Filed by RINA with drawing SHEL-18036.
Reference Documents Technical drawings and manuals approved and filed by RINA listed on Approval letter No.: SHEL/2024/23/ZHITA, SHEL/2024/27/ZHITA, SHEL/2024/60/ZHITA, SHEL/2024/66/ZHITA and SHEL/2024/108/ZHITA. |