MED483221CSENGB- -  -  N- AQUATECH ® TS-WMC16 -N- S- S- -17/01/2022- Marine Equipment- - SN- S- - N-  - 151,598B2bisMarine EquipmentNumero Pratica,Direttiva,Norma,Schema,Richiesta,Validità- MED483221CS- N-Jan 16, 2027151598
 
Form
  Marine Equipment(TO)
MED483221CS
Certification N. MED483221CS - (ENG)
Certificate date 17/01/2022
Type Protezione antincendio
Product Galley Exhaust Duct Fixed Fire Extinguishing Systems components
Item Nº MED/3.68

Model or Denomin.
Items
AQUATECH ® TS-WMC16
Applicant TEMA SISTEMI SPA
Place of requester VIA LUCIANO ROMAGNOLI N. 4  %  48026 Russi (RA)  % ITALY
Tel. N.,Fax, Email 0544 471350, 0544 471350, ufficio.qualita@temagroup.eu
Directive (EU) 2021/1158
Standards ISO 15371: 2015
Reference Documents Chap. II-2 of SOLAS 74 Convention, as amended
Expire date 16/01/2027
EC TYPE-EXAMINATION (MODULE B) ENG
Vuoto Querysave
Giovanni Carratino S

EC TYPE EXAMINATION (MODULE B)
CERTIFICATE No. MED483221CS

This is to certify that RINA Services S.p.A. (Notified Body No. 0474) did undertake the relevant type approval procedures for the equipment identified below, which was found to be in compliance with the Fire Protection requirements of Marine Equipment Directive (MED) 2014/90/EU, including the requirements and testing standards of Regulation (EU) 2021/1158.
MED Item Nº MED/3.68
Description Galley Exhaust Duct Fixed Fire Extinguishing Systems components
Type AQUATECH ® TS-WMC16
Applicant TEMA SISTEMI SPA
VIA LUCIANO ROMAGNOLI N. 4,48026 Russi (RA),ITALY
Testing standards ISO 15371: 2015
Reference standards Chap. II-2 of SOLAS 74 Convention, as amended
Issued in Genoa on
This Certificate is valid until
January 17, 2022
January 16, 2027
This Certificate consists of this sheet plus an attachment

________________________________________
Giovanni Carratino
RINA Services S.p.A.
**** NOTICE: This is NOT an official certificate ****

ATTACHMENT TO
CERTIFICATE No.  MED483221CS
Page 1 of 3

System description

“Aquatech ®” is a manually/automatically operated water mist system consisting of nozzles, stainless steel piping, section valves, filters, control system and water supply pump(s).
Only the nozzles AQUATECH ® TS-WMC16 are within the scope of this certificate.
Pumps, pipes, valves, couplings and other systems components are subject to case by case approval.
Nozzle characteristics
- Material: brass OT58.
- Spray and steaming: radial 360°.
- Functioning: pop-up.
- Mist: from 50 to 150 micron.
- Filter: interchangeable stainless steel filter.
- Test pressure: 150 bar.
- Working pressure: 100 bar.
- Flow rate: 6,1 lt/min.
- Max installation spacing*: 10 m for ducts having cross section area not exceeding 0.5 m².

* for ducts having a cross sectional area more than that above specified, the arrangement will be evaluated case by case (reduced spacing).
Fields of application

Local protection for galley extract duct limited to a cross sectional area* of 0.5 m2.

Nozzle installation requirements

Projection Discharge
perpendicular to the ducts
Max spacing from each nozzle *
10 m
K factor (lpm/bar1/2)
0.61 l/min
Minimum working pressure
100 bar
Maximum duct free sectional area *
0.5 m2




ATTACHMENT TO
CERTIFICATE No. MED483221CS
Page 2 of 3
Reference documents

- Sprayhead TS-WMC16, dwg n° TS031- Rev 1, issued by Tema Sistemi S.p.A. and approved by RINA with n° CSST-19767.
- Design, installation, operation and maintenance manual "MANUALE DI USO E INSTALLAZIONE SISTEMA DI SPEGNIMENTO AD ALTA PRESSIONE CON UGELLI TS-WMC16", dwg n° TS-MAN-WMC16 issued by Tema Sistemi S.p.A. and filed by RINA with n° CSST-19768.
- Nozzle datasheet, issued by by Tema Sistemi S.p.A. and filed by RINA with n° CSST-19809.
- Test report n° TS-WM/CM/01/19 issued by Brand Technology S.r.l. for Tema Sistemi S.p.A and filed by Rina with n° CSST-19810.
Remarks

a) Installation of the system, spacing of nozzles and components used shall be in accordance with the type approval documentation;
b) Prior to fitting the system on board, the following details shall be submitted for approval for each installation:
- Ducts layout and nozzles arrangement;
- Schematic arrangement of the system including sizes and material of piping and method of pipe jointing, nozzle types;
- Specification of the pump unit;
- Hydraulic calculation.
c) The nozzles shall be marked with the name of the producer and the type designation as indicated in this certificate.




ATTACHMENT TO
CERTIFICATE No. MED483221CS
Pages 3 of 3
The mark of conformity may only be affixed to the above type approved equipment and a Manufacturer's Declaration of Conformity issued when the production control phase module (D, E or F) of Annex II of the Directive is fully complied with a written inspection agreement with a Notified Body
XXXX/YY
"WHEELMARK FORMAT"

XXXX
Notified Body number undertaking surveillance module
YY
Last two digits of year mark affixed
     
______________________________________________
General conditions for the approval
a) The initial conditions verified by RINA at the time of the approval are to be maintained
b) Any changes to the initial conditions are to be promptly communicated to RINA, which reserves the right to repeat the relevant assessment
c) This certificate will no be valid if the manufacturer makes any changes or modifications to the approved equipment, which have not been notified to, and agreed with RINA
d) RINA personnel are to be allowed to witness during the performances of activities, upon their request
e) The activities are to be carried out in compliance with the RINA Rules and/or other applicable Rules

f) Should the specified regulations or standards be amended during the validity of this certificate, the product is to be reapproved prior to it being placed on board vessels to which the amended regulations or standards apply. 


__________________________________________
Giovanni Carratino
**** NOTICE: This is NOT an official certificate ****