Mobile Water Monitor is used for Protection of On Deck Container Stacks, in accordance with Reg.II-2/10.7.3.2 of SOLAS '74 as amended.
Technical Data
Main Components of Mobile Water Monitor: Inlet fitting, Monitor waterway, Swivel fittings, Discharge nozzle and a shut-off device, Carrying handle.
Nominal Capacity: 63 m3/h (1050 L/min) @ 0.4 Mpa
Nominal Working Pressure: 0.4 Mpa
Hydrostatic Test Pressure: 0.7 Mpa
Minimum Horizontal Throw Length: 42 meters @ 0.4 Mpa
Pivoting Area: Horizontal, 270 °, Vertical, -90 ° to + 90 °
Weight: ≤ 23 Kg
Nozzle Type: Dual-purpose Spray/Jet
Water Inlet Dimension: 2.5 Inch
Corrosion Resistant Materials: Cast Aluminum, Aluminum, Stainless Steel
Reference Document
The design assessment is based on IMO Resolution MSC.365(93) with following documents:
- Technical Drawing of Mobile Water Monitor, issued by Shanghai Firetec Mechatronic Engineering Co., Ltd and approved by RINA with No.: SHFP-13807;
- Instruction Manual, issued by Shanghai Firetec Mechatronic Engineering Co., Ltd and filed by RINA with No.: SHFP-13810;
- Instructions for Safe Operation and Maintenance, issued by Shanghai Firetec Mechatronic Engineering Co., Ltd and filed by RINA with No.: SHFP-14871;
- Technical Specification, issued by Shanghai Firetec Mechatronic Engineering Co., Ltd and filed by RINA with No.: SHFP-14873.
 | ATTACHMENT TO
CERTIFICATE No. MED243825WS
Page 2 of 3 |
Production and Tests
The production must be carried out in accordance to the manufacturer quality production system.
Tests has been carried out and witnessed by RINA Surveyor in compliance with IMO MSC.1/Circ.1472 (Guidelines for the design, performance, testing and approval of mobile water monitors used for the protection of on-deck cargo areas of ships designed and constructed to carry five or more tiers of containers on or above the weather deck). Relevant Test Report issued by Shanghai Firetec Mechatronic Engineering Co., Ltd has been filed by RINA with No.: SHFP-13812.
Mobile Water Monitor Test Report,has been filed by RINA with No.: SHFP-31031.
Remark
Mobile Water Monitors should be equipped with a coupling allowing connection to the ship's fire hydrants by fire hoses. The coupling should be sized so as to ensure that the flow and pressure needed for correct performance will be provided.
The manufacturer's operating guidelines includes information on the safe operation of the monitors to be observed.
Note
Renewal of Initial EC Type Examination (Module B) Certificate No.: MED057319WS. As declared, the initial conditions at the time of the approval are maintained, without any change.