Marine pneumatic, manual and motorized fire dampers on bulkhead. Dimensions of fire damper was: Specimen A 1600x1400 mm, Specimen B 800x800 mm and Specimen C 450x600 mm.
Specimen A TFDD-1600x1400-QA-R: this fire damper was equipped, on the outer surface, by a pneumatic actuator type SR85 produced and provided by Wuxi St.Hans Pneumatic Valve Actuator Manufacturing Co.Ltd. The fire damper was fixed to the coaming by thirty-two M8mm steel bolts, and was padded with 20mm of ceramic wool.
Specimen B TFDD-800x800-SA: this fire damper was equipped, on the outer surface, by a manual actuator type DL-CII-3 produced and provided by Ningbo East Spirit of Plumbing Air Conditioning Part Co.,Ltd. The fire damper was fixed to the coaming by eighteen M8mm steel bolts, and was padded with 20mm of ceramic wool.
Specimen C TFDD-450x600-ZA: this fire damper was equipped, on the outer surface, by an motorized actuator type BFN-230 produced and provided by Belimo Actuators (Shangai) Trading Ltd. The fire damper was fixed to the coaming by fifteen M8mm steel bolts, and was padded with 20mm of ceramic wool.
The fire dampers and its operative control were positioned on the exposed side of the bulkhead and was fixed to the coaming and the coaming was fixed to the bulkhead structural core by welding. For each fire dampers the blade was 30 mm thick, of composite structure, which was composed, from the exposed side, of 2 mm steel plate, a layer of ceramic wool and 2 mm steel plate. The insulating material used on fire damper was TG type ceramic wool produced by Zhejiang Province Deqing County Pusen Fireproof Material Co., Ltd. having thickness of 25 mm and density of 170 kg/m3 (certified non-combustible in compliance with IMO FTP Code).
|
ATTACHMENT TO
CERTIFICATE Nr. MED112926CS
Page 2 of 3 |
Field of application
Fire resistant A-60 Class fire dampers fitted on bulkhead as per the following table:
item | Maximum
Ventilation
Size
(mm) | Maximum External
Size
(mm) | Penetration
lenght
(mm) | Coaming
Thickness
(mm) | Damper body
(mm) | Distance between
damper and
structural core
(mm) | Actuator
type |
TFDD | 1600x1400 | 1676x1476 | 320 | 8 | 8 | 230 | Pneumatic |
800x800 | 1676x1476 | 320 | 6 | 8 | 230 | Manual |
450x600 | 526x676 | 320 | 6 | 6 | 260 | Motorized |
Reference documents
Drawings enclosed to FEFTC, Far East Fire Testing Centre, Report No. FT18212 dated 25 September 2018 and Report No. FT18213 dated 25 September 2018.
Tests carried out
Tests as per FEFTC, Far East Fire Testing Centre, Report No. FT18212 dated 25 September 2018 and Report No. FT18213 dated 25 September 2018 according to IMO 2010 FTP Code Part. 3 - Annex 1. |