Materials/Components
Marine power cables designed according to IEC 60092-353.
Rated voltage: 0,6 / 1 kV
Maximum rated conductor temperature: + 90 oC
Type: LSM-HF (1XC4Z1-R, 1XC4Z1-K), LM-HF (1XZ1-R, 1XZ1-K), LM-FRHF (1J2XZ1-R, 1J2XZ1-K), LSM-FRHF (1J2XC4Z1-R, 1J2XC4Z1-K), LSM-HF EMC (1XC7Z1-R, 1XC7Z1-K)
Marking: PRYSMIAN -AFUMEX MARINE CABLES - TYPE -SIZE - 0.6/1 kV - IEC 60092-353 - IEC 60332-3/A + YEAR + metric marking (by ink)
(For FR cables) PRYSMIAN -AFUMEX MARINE CABLES - TYPE -SIZE - 0.6/1 kV - IEC 60092-353 - IEC 60332-3/A - IEC 60331 + YEAR + metric marking (by ink)
Construction
Conductors: R types: Stranded copper conductor, class 2
K types: Flexible stranded copper conductor, class 5
Mica Tape: Only for J (FR) typed cables
Core Insulation: HF XLPE
Inner Covering: LSOH filler / LSOH inner covering or tape
Metal Covering: Bare copper wire braiding (only for C4 and C7 typed)
Screen: Electro Magnetic Compatible (EMC) 100% covered copper tape screen (EMC cables only)
Outer Sheath: SHF1
No of Elements: 1 to 6 / Cross-sectional area 1,5 to 300 mm2
No of Elements: 7 to 60 / Cross-sectional area 1,5 to 4 mm2
Reference documents : Test Report: Türk Prysmian Kablo 20250029, dated 14.05.2025
Reference Standards: IEC60092-350; IEC60092-353; IEC60092-360; IEC 60228; IEC 60332-3-22 cat A; IEC 60332-1-2; IEC 61034-1/2; IEC 60754-1/2; IEC 60331-11; IEC 60331-21; RINA Rules for the Classification of Ships; RINAMIL; RINA Rules for FPV; RINAMIL for FREMM; RINA Rules for Floating Offshore Units and MODU.